LDS02 LoRaWAN Door Sensor ​

LDS02 is a native LoRaWAN Class A sensor powered by two AAA batteries. A sensor and magnet detect door state, opening count and last opening duration. Product information and the photograph are from the official Dragino manual.

LDS02 LoRaWAN Door Sensor

LDS02

Installation and onboarding ​

Mount the sensor on the frame and magnet on the door. Align their marks with the door closed and verify both states on site. Register the actual network credentials, check the frequency region and select the LDS02 template. The default upload interval is 86400 seconds and downlink port is 2. Class A delivery uses receive windows following uplinks.

Data and configuration ​

Inspect battery, state, event count and last duration. Each settings RPC selects one operation: upload interval, confirmed uplinks, event uplinks or ADR/DR. LDS02 also exposes device-side door-open timeout (0 disables it) and EDC open/close counting. In EDC mode read edc_state/edc_count; do not assume ordinary-frame fields still apply. The maintenance RPC supports explicit reset or cumulative-count clearing, without automatic retries.

Alarms and acceptance ​

The template links the door-timeout trigger. Check binding, an actual event report, alarm creation and recovery separately. Notification groups and channels require additional setup. The parameter model's rpc_hook_status does not establish that all settings were applied. Verify fresh reports, observed intervals and physical events; queueing is not completion.

Model catalog ​

Model typeNameid_namePlatform model ID
TemplateLDS02147733851588685839
Thing Model[LDS02]lds02_21316147733851592880128
Thing Model[LDS02-PARA]lds02_para_21316147733851592880129
RPC[LDS02 ACTION] 21316lds02_action_21316147733851592880131
RPC[LDS02 SET] 21316lds02_set_21316147733851592880130
Trigger[LDS02] Door Timeout Trigger147733851592880132

Data fields ​

lds02_21316 ​

FieldMeaningTypeUnit
batteryBatterynumberV
frame_modeFrame Modestring
door_open_statusDoor Open Statusnumber
modeModenumber
total_open_eventsTotal Open Eventsnumbercount
last_open_durationLast Open Durationnumbermin
alarm_statusDoor Timeout Alarmnumber
edc_stateEDC Count Statestring
edc_countEDC Countnumbercount
rssiRSSInumberdBm
snrSNRnumberdB
adrADRboolean

lds02_para_21316 ​

FieldMeaningTypeUnit
rpc_hook_statusRPC Match Statusstring

Model names and IDs were checked against the ThinkLink PUBLIC catalog on 2026-10-13. Catalog availability does not establish field wiring, firmware installation or physical control acceptance.