The original PKO-DEHUM-21309 template provides acquisition parameters, power and setpoint RPCs, plus optional automatic control and fault alarms. For basic protocol onboarding, see the new PUBLIC profile. The two profiles have different model IDs.

PARKOO Legacy PUBLIC Models and Automation

Onboarding and operation ​

Use a continuously powered Class C KC11, RS-485 9600, 8N1, and the actual dehumidifier address. Match business firmware 21309. Read parameters and fresh measurements before issuing power or setpoint operations; confirm results from subsequent observations. Load working-state bits and fault bits have different meanings: a running fan bit is not a fan fault.

Automatic control, alarms and notifications ​

Automatic control uses an enable flag, humidity upper/lower thresholds and time windows. The upper threshold requests power on and the lower requests power off; choose a suitable hysteresis gap. These are control thresholds, not independent high/low humidity alarm limits. Bind the control trigger as needed and check window schedules and device configuration. A separate trigger handles faults; delivery also needs notification groups and channels. Template existence does not establish an enabled policy or a received notification.

Verification ​

Check bindings, enablement, schedules and notification configuration, then observe actual telemetry triggers and control feedback. Manually clearing an alarm does not repair a physical fault; a later fault report may recreate it. The aggregation model summarizes data and does not operate the dehumidifier.

Model catalog ​

Model typeNameid_namePlatform model ID
TemplatePKO-DEHUM-21309113320402519748613
Thing Model[PKO-21309-DEHUM资产] 区域聚合pko_asset_21309119677174411063299
Thing Model[PKO-PARA]pko_para_21309113320402519748609
Thing Model[PKO]pko_21309113320402519748608
RPC[PKO SETPOINT ACT]pko_setpoint_action_21309115140981942022144
RPC[PKO ACT] 消除告警pko_clear_alarm_21309114694389782966275
RPC[PKO POWER ACT]pko_power_action_21309114414111818674180
RPC[PKO ACT] 自控事件通知pko_autoctrl_notify_21309114694389782966272
RPC[PKO GET] parapko_get_21309113320402519748611
RPC[PKO SET] 自控配置pko_autoctrl_config_21309114694389782966274
RPC[PKO SET] parapko_set_21309113320402519748610
RPC[PKO ACT] 定时窗口标志pko_autoctrl_window_21309114694389782966273
Trigger[PKO] 除湿机故障告警触发器114694389782966277
Trigger[PKO] 除湿机定时窗口湿度自控触发器114694389782966276
Trigger[青岛中糖]除湿机全天候湿度自控触发器115512995995445930

Data fields ​

pko_asset_21309 ​

FieldMeaningTypeUnit
on_power_switch_cntZone Power Switchnumber
zone_temperature_avgZone Temperaturenumber℃
zone_humidity_avgZone Humiditynumber%RH
zone_temp_set_avgZone Temperature Setpointnumber℃
zone_humidity_set_avgZone Humidity Setpointnumber%RH
on_fan_cntZone Fannumber
on_compressor_1_cntZone Compressor 1number
on_compressor_2_cntZone Compressor 2number
on_heating_cntZone Heating Elementnumber
zone_coil_temp_1_avgZone Coil Temperature 1number℃
zone_coil_temp_2_avgZone Coil Temperature 2number℃
zone_coil_temp_3_avgZone Coil Temperature 3number℃
zone_coil_temp_4_avgZone Coil Temperature 4number℃
online_countZone Online Countnumber

pko_para_21309 ​

FieldMeaningTypeUnit
addr_modbusModbus Addressnumber
period_upUpload Periodnumbers
rssiRSSInumberdBm
snrSNRnumberdB
temp_setTemperature setpointnumber℃
period_readCollect Periodnumbers
humidity_setHumidity setpointnumber%RH
cov_temperatureTemperature Change Thresholdnumber℃
cov_humidityHumidity Change Thresholdnumber%RH
period_heartperiod_heartnumbers
command_rpcCommand RPCstring
command_idCommand identitystring
command_statusCommand feedback statusstring
command_observed_atFeedback timestring

pko_21309 ​

FieldMeaningTypeUnit
power_switchPower Switchnumber
temperatureTemperaturenumber℃
humidityHumiditynumber%RH
temp_setTemperature Setpointnumber℃
humidity_setHumidity Setpointnumber%RH
fanFannumber
compressor_1Compressor 1number
compressor_2Compressor 2number
heatingHeating Elementnumber
run_modeRun Modestring
load_outputLoad Output StatusstringHEX
fault_textFault Statusstring
fault_statusFault CodestringHEX
coil_temp_1Coil Temperature 1number℃
coil_temp_2Coil Temperature 2number℃
coil_temp_3Coil Temperature 3number℃
coil_temp_4Coil Temperature 4number℃

Model names and IDs were checked against the ThinkLink PUBLIC catalog on 2026-10-13. Catalog availability does not establish field wiring, firmware installation or physical control acceptance.

Historical all-day trigger ​

The platform still lists ID 115512995995445930 as PUBLIC, while its remark identifies a customer-specific variant. It uses all-day humidity hysteresis without a time-window check and requests a humidity setpoint of 10 before power-on. This entry identifies existing bindings only. Do not adopt it for a new deployment without reviewing policy ownership, device protocol and alarm/notification requirements. The model owner should reconcile the visibility and remark inconsistency.