HW-58D Water Leak Sensor ​

HW-58D connects through the KC11 RS-485 interface. It distinguishes dry, water-leak and disconnected-probe states for equipment rooms, pump rooms and service shafts.

HW-58D Water Leak Sensor

Wiring and onboarding ​

Connect RS-485 A to A and B to B. Power the sensor separately according to its nameplate. The available protocol does not establish its supply voltage or wire colors. Use 9600, 8N1, slave address 2, and a continuously powered Class C KC11. Select HW-58D-21314, install the matching EdgeBus application (business code 21314, version 1), and check the regional radio settings.

Sampling and alarms ​

The default sampling interval is 5 seconds, with a maximum 300-second upload interval when the state is unchanged. State changes trigger COV uploads. alarm_status is 0 for normal, 1 for water leakage and 2 for a disconnected probe or sensing cable. The template includes the water-leak trigger; normal readings clear both alarms. Configure notification channels and recipients separately.

Configuration and acceptance ​

Read parameters before changing sampling, upload or heartbeat intervals. The sensor configuration RPC exposes alarm delay, sensitivity, buzzer and probe type, but not the device address or baud rate. Delay is 0–120 seconds; sensitivity 1/2/3 means high/medium/low. Verify dry, wet and disconnected states, recovery, and alarm records. An accepted RPC or queued downlink is not device feedback.

Model catalog ​

Model typeNameid_namePlatform model ID
TemplateHW-58D-21314345508976621785096
Thing Model[HW-58D-PARA]hw58d_para_21314345510208384012289
Thing Model[HW-58D]hw58d_21314345510208384012288
RPC[HW-58D CONFIG] 21314hw58d_config_21314345508976621785094
RPC[HW-58D GET] 21314hw58d_get_21314345508976621785093
RPC[HW-58D SET] 21314hw58d_set_21314345508976621785092
Trigger[HW-58D] Water Leak Trigger345508976621785095

Data fields ​

hw58d_para_21314 ​

FieldMeaningTypeUnit
pwron_delayPower-on Delaynumberms
period_heartHeartbeat Periodnumbers
period_upUpload Periodnumbers
period_readCollect Periodnumbers
cov_alarm_statusAlarm Status COVnumber
addr_modbusModbus Addressnumber
rssiRSSInumberdBm
snrSNRnumberdB
TimeOffsetTime Offsetnumber
alarm_delayalarm_delaynumbers
alarm_sensitivityalarm_sensitivitynumber
buzzer_enablebuzzer_enablenumber
probe_typeprobe_typenumber
command_rpcCommand RPCstring
command_idCommand identitystring
command_statusCommand feedback statusstring
command_observed_atFeedback timestring

hw58d_21314 ​

FieldMeaningTypeUnit
alarm_statusAlarm Statusnumber
alarm_delayAlarm Delaynumbers
alarm_sensitivityAlarm Sensitivitynumber
firmware_versionFirmware Versionnumber
statusCommunication Statusnumber
batteryDTU VoltagenumberV
rssiRSSInumberdBm
snrSNRnumberdB

Model names and IDs were checked against the ThinkLink PUBLIC catalog on 2026-10-13. Catalog availability does not establish field wiring, firmware installation or physical control acceptance.