PARKOO Dehumidifier PUBLIC Integration ​

Select PKO-DEHUM-21309-PUBLIC to connect the device through KC11. This generic profile provides telemetry, parameter operations and feedback without customer automation, notification groups or site locations.

PARKOO Dehumidifier PUBLIC Integration

Wiring and preparation ​

Use continuously powered Class C, RS-485 9600, 8N1, and default polling address 1. Match A/B wiring to the nameplate and manufacturer protocol. Install the EdgeBus application for 21309 / v3 and check regional radio settings. Selecting the template does not install firmware or change the dehumidifier's panel address. Polling addresses are 1–247.

Daily operation ​

Inspect fresh temperature, humidity, power, fault and timestamp values before changing power or the humidity setpoint (10–99). Temperature setpoints are 10–65 °C. Fan, compressors, heater and coil states are available; disabled coil probes do not produce valid temperatures. Power state is not proof of compressor motion.

Writes and feedback ​

A power command writes once and queues one read 10 seconds later, within a total 30-second observation window. A write acknowledgement is only an acknowledgement. Confirm the actual result from a valid read or fresh report. Missing, expired or failed communication means unknown/unconfirmed, with no automatic repeated write. Serialize transparent operations per device: the protocol has no request ID, so identical delayed replies can remain ambiguous.

Sampling and location ​

Defaults are 60 seconds for sampling, 300 seconds for uploads and 900 seconds for the collector heartbeat. These intervals are independent. Temperature/humidity COV defaults are 1 °C / 2 %RH; SET includes one collector reset. Faster sampling adds serial load; faster uploads add radio traffic. Use readback for actual values.

The 3D-location action accepts a location object containing scene_id, model_id, coordinate_system, unit and x/y/z position. Read back _location_3d; this does not change the formal location assignment.

Acceptance scope ​

PUBLIC resources were published and read back. Physical actions, natural acquisition cycles, business MQTT, persistent logs and application waiting states still require field acceptance. The complete integration gate retains failed or environment-blocked checks; catalog availability is not end-to-end acceptance. Configure alarm and automatic-control policies separately.

Model catalog ​

Model typeNameid_namePlatform model ID
TemplatePKO-DEHUM-21309-PUBLIC162605506869751808
Thing ModelPKO公共采集参数pko_public_para_21309162605506869751810
Thing ModelPKO公共实时数据pko_public_21309162605506869751809
RPC设置采集参数pko_public_set_21309162605506869751811
RPC保存3D模型位置pko_public_location_21309162605506869751815
RPC除湿机开关机pko_public_power_21309162605506869751813
RPC设置温湿度pko_public_setpoint_21309162605506869751814
RPC读取采集参数pko_public_get_21309162605506869751812

Data fields ​

pko_public_para_21309 ​

FieldMeaningTypeUnit
period_heartHeartbeat intervalnumbers
period_upUpload intervalnumbers
period_readSample intervalnumbers
cov_temperatureTemperature change thresholdnumber℃
cov_humidityHumidity change thresholdnumber%RH
addr_modbusModbus addressnumber
parameter_observed_atParameter observation timestring
command_idCommand identitystring
command_rpcCommand RPCstring
command_statusCommand statusstring
command_observed_atCommand observation timestring

pko_public_21309 ​

FieldMeaningTypeUnit
power_switchPower Switchnumber
temperatureTemperaturenumber℃
humidityHumiditynumber%RH
temp_setTemperature Setpointnumber℃
humidity_setHumidity Setpointnumber%RH
fanFannumber
compressor_1Compressor 1number
compressor_2Compressor 2number
heatingHeating Elementnumber
run_modeRun Modestring
load_outputLoad Output StatusstringHEX
fault_textFault Statusstring
fault_statusFault CodestringHEX
coil_temp_1Coil Temperature 1number℃
coil_temp_2Coil Temperature 2number℃
coil_temp_3Coil Temperature 3number℃
coil_temp_4Coil Temperature 4number℃
statusSample status bytenumber
batterySupply voltagenumber
rssiRSSInumber
snrSNRnumber
communication_okCommunication OKboolean
source_sample_timeValid sample timestring
power_expires_atState expiry timestring
report_received_atReport receive timestring
command_idCommand identitystring
command_rpcCommand RPCstring
command_statusCommand statusstring
command_observed_atCommand observation timestring
fan_low_speedLow fan speednumber
humidity_controlHumidity controlnumber
defrostDefrostnumber
protectionProtectionnumber
fault_waterWater fullnumber

Model names and IDs were checked against the ThinkLink PUBLIC catalog on 2026-10-13. Catalog availability does not establish field wiring, firmware installation or physical control acceptance.